Automatic monitoring and alert systems over the Network and Cellular Network (mobile phone network), for Data Centers, Server Rooms, Facility Rooms, Warehouses, medicine refrigerators and other critical areas 081-712-1000 · 090-970-5830 · LINE 063-215-8620

Standalone

VUTLAN

VUTLAN is a controller for environmental monitoring and device control. It works with Analog sensors, CAN-bus devices and Dry Contact, and can collect data from other network devices via SNMP v1, v2c, v3 and Modbus TCP/IP. Modbus RTU (RS-485) is supported when an add-on module is installed.

Highlights of VUTLAN

Suited to projects that need to install and use right away with no software to install, and need to connect to other systems

Standalone, no software installation needed

After installation, configure via the unit's web interface. All features are built in.

Third-party system integration

Receives Dry Contact input signals from other devices, Modbus RTU (RS-485) via the VT485m or VT485m ISO module (sold separately), and collects data from other network devices via SNMP v1/v2c/v3 and Modbus TCP/IP

Ports full

Analog port, CAN bus, Dry Contact; expandable with VT408 (Analog) and VT440 (Dry Contact) modules

Built-in LTE

An LTE module can be installed directly in the unit's slot with no separate USB modem (module sold separately; insert a SIM)

Multi-channel alerts

Email, Telegram, LINE OA (limited to 300 messages/month) via the MT Notify service, and SMS when an LTE module is fitted

Management software used with VUTLAN

NameFormatWhat it does
MT Monitor (by Monitoring Technology)Installed on your organization's Windows serverReal-time dashboard, offline site map, Email/Telegram alerts, PDF reports, Event/Audit Log; supports Room Alert, VUTLAN and HWg via SNMP
VUTLAN works standalone right away with no software to install. MT Monitor is an option when you want to view multiple sites together.

Compare models

Ports / capabilities VT225tVT335GVT336tVT825GVT855G
Dry Contact input ★ 2481632
Analog port (RJ12) 44488
Relay 12V 0.25A 22222
CAN bus devices 3131–2424
Dry Contact output ––5–8
Relay NC/NO/COM –––22
Alerts Email Support Support Support Support Support
Alerts LINE OA Support Support Support Support Support
Alerts Telegram Support Support Support Support Support
Alerts SMS Not supported Add-on equipment required Add-on equipment required Add-on equipment required Add-on equipment required

★ Dry Contact input Port for dry-contact (on/off) signals from sensors or other devices such as doors, smoke, water leak and UPS

Modules and accessories

NameAdd portsNote
VT408 Analog sensor extension unitVT408 Analog sensor extension unit
Analog port (RJ12) +8 Adds 8 Analog ports per unit, connected via CAN bus
VT440 Dry contacts unitVT440 Dry contacts unit
Dry Contact input +32 Adds 32 Dry Contact inputs per unit, connected via CAN bus
VT440 + VT32 Dry contacts unitVT440 + VT32 Dry contacts unit
Dry Contact input +64 Adds 64 Dry Contact inputs per unit (the VT32 is an add-on board in the VT440)
VT485m Modbus RTU (RS-485) moduleVT485m Modbus RTU (RS-485) module
– Installs in the unit's Extension slot; supports up to 32 Modbus RTU devices with up to 1,000 m of cable. It uses the same slot as the VT485m ISO and VT485r, so they cannot be used together.
LTE ModemLTE Modem
– Sold separately. Installs in the slot inside the unit and takes a SIM card (not a USB modem). The module model/part number depends on the controller model.
VT-BAT / VT-ACCU battery extensionVT-BAT / VT-ACCU battery extension
– Backup battery for models with a battery compartment
VT485m ISO Modbus RTU (RS-485) moduleVT485m ISO Modbus RTU (RS-485) module
– The ISO Modbus RTU module uses the same Extension slot as the VT485m and cannot be used together with it. This model is not found on the manufacturer's VT335G / VT825G / VT855G product pages. Confirm the spec and compatibility with the manufacturer.
VT408D Sensor extension unit (DIN)VT408D Sensor extension unit (DIN)
Analog port (RJ12) +8 The DIN-rail version of the VT408 adds 8 Analog ports per unit
CAN-12V-1A CAN bus power supplyCAN-12V-1A CAN bus power supply
– Recommendedเมื่อมีCAN bus devices เกิน 5 Equipment (ต่อ Adapter เสียบปลั๊กไฟ)

Compatible sensors and probes

EquipmentUses portsDetails
Temperature sensor
Temperature sensor
VT500
Analog port (RJ12) ×1 Plug & play analog temperature sensor
Outdoor temperature sensor
Outdoor temperature sensor
VT515
Analog port (RJ12) ×1 Analog temperature sensor for outdoor installation
Humidity sensor
Humidity sensor
VT510
Analog port (RJ12) ×1 Analog humidity sensor
Water leak sensor (for use with WLC cable)
Water leak sensor (for use with WLC cable)
VT591 + WLC
Analog port (RJ12) ×1 Water leak detection along a WLC cable (sold separately in 10/15/25 m lengths, chainable up to 100 m in total per VT591)
Spot water leak sensor
Spot water leak sensor
VT593
Analog port (RJ12) ×1 Spot water leak detection, e.g. under air conditioners or raised floors
Smoke detector
Smoke detector
VT560
Analog port (RJ12) ×1 Analog smoke detector, can be daisy-chained in series
Motion sensor (radar)
Motion sensor (radar)
VT572
Analog port (RJ12) ×1 Radar motion sensor for motion detection
Vibration sensor
Vibration sensor
VT540
Analog port (RJ12) ×1 Vibration detection
AC voltage monitor
AC voltage monitor
VT520
Analog port (RJ12) ×1 AC voltage monitoring
Temperature + humidity sensor (CAN)
Temperature + humidity sensor (CAN)
VT490
CAN bus devices ×1 Temperature and humidity sensor on the CAN bus
Pressure + humidity + temperature sensor (CAN)
Pressure + humidity + temperature sensor (CAN)
VT450
CAN bus devices ×1 Measures temperature, humidity, dew point and air pressure
Smoke + humidity + temperature sensor (CAN)
Smoke + humidity + temperature sensor (CAN)
VT460
CAN bus devices ×1 Smoke detection with humidity and temperature measurement
Dry Contact signals from other devices (UPS, control cabinets, door switches)
Dry Contact signals from other devices (UPS, control cabinets, door switches)
Dry Contact
Dry Contact input ×1 Connects a dry contact from any device. Never apply voltage to the port.
Control 12V devices (small sirens/signal lights)
Control 12V devices (small sirens/signal lights)
Relay 12V 0.25A
Relay 12V 0.25A ×1 Uses a 12V 0.25A relay. Check the load current of your device before use.
Control devices via NC/NO/COM contacts
Control devices via NC/NO/COM contacts
Relay NC/NO/COM
Relay NC/NO/COM ×1 Switch external equipment on/off via a relay
Modbus RTU (RS-485) devices
Modbus RTU (RS-485) devices
Modbus RTU
– Collecting data from Modbus RTU devices requires an additional VT485m or VT485m ISO module
AC voltage monitor (DIN rail)
AC voltage monitor (DIN rail)
VT520DIN
Analog port (RJ12) ×1 DIN-rail AC voltage monitor
Door sensor (access sensor)
Door sensor (access sensor)
VT530
Analog port (RJ12) ×1 Door open/close detection
Wind speed sensor (anemometer)
Wind speed sensor (anemometer)
VT550
Analog port (RJ12) ×1 Measures wind speed
Dust sensor
Dust sensor
VT580
Analog port (RJ12) ×1 Dust particle measurement
DC voltage monitor
DC voltage monitor
VT410
Analog port (RJ12) ×1 DC voltage monitoring
AC current transducer
AC current transducer
VT405
Analog port (RJ12) ×1 AC current transducer (current converter)
KMS-30 magnetic door switch
KMS-30 magnetic door switch
KMS-30
Dry Contact input ×1 Contact magnet sensor, dry contact, connects to a Dry Contact port
KMS-37 magnetic switch (3-wire NC/NO)
KMS-37 magnetic switch (3-wire NC/NO)
KMS-37
Dry Contact input ×1 3-wire NC/NO contact magnet sensor, connects to a Dry Contact port
WLC water leak cable, 10 m
WLC water leak cable, 10 m
WLC 10M
– 10 m water leak cable for VT591, sold separately. Uses no extra port; can be chained up to 100 m in total per VT591.
WLC water leak cable, 15 m
WLC water leak cable, 15 m
WLC 15M
– 15 m water leak cable for VT591, sold separately. Uses no extra port; can be chained up to 100 m in total per VT591.
WLC water leak cable, 25 m
WLC water leak cable, 25 m
WLC 25M
– 25 m water leak cable for VT591, sold separately. Uses no extra port; can be chained up to 100 m in total per VT591.
Light Tower, 3 colors (red/yellow/green)
Light Tower, 3 colors (red/yellow/green)
VT109
Relay 12V 0.25A ×1 3-color signal tower: green = normal, yellow = warning, red = alarm. 12V DC 70 mA, 2 m cable, IP54. Mounts on a desk, wall or inside a rack.
Strobe light
Strobe light
VT105
Relay 12V 0.25A ×1 Red/white flashing light, 12V DC 120 mA, 2-wire red/black cable 3 m, IP54. Mounts on a wall, ceiling or cabinet.
Siren with flashing light (Alarm Beacon)
Siren with flashing light (Alarm Beacon)
VT103
Relay 12V 0.25A ×1 108 dB siren with red flashing light, 12V DC, 3 m cable, IP54. Wall mount.

Trusted by

Customers and partners who trust us

Consult our team