AN01 Perseus M-Bus Inepro PRO1
This guide describes the basic setup of the HWg Perseus device and the Inepro PRO-Mb M-Bus electricity meter.
This guide describes the basic setup of the HWg Perseus device and the Inepro PRO-Mb M-Bus electricity meter.
It covers the connection of the devices, M-Bus configuration, meter integration into Perseus, loading and configuring measured values, and final setup in the SensDesk cloud for monitoring and alarms.
For more details, refer to the following manuals:
https://www.hw-group.com/product-version/perseus-man
https://www.ineprometering.com/product/pr01-mb-electricity-meter
Support1) Connecting the HWg Perseus Device and Inepro PRO1-Mb
Connect the Perseus device to the electricity meter via the MBUS port. Use a daisy-chain or star topology without termination resistors.
Connect the Perseus device to the LAN network (Ethernet) and to the power supply.
2) Configuration of the M-Bus Parameters on the Meter
The defaults for M-bus communication are:
– The secondary address is preset to the last 8 digits of the serial number printed on the side of the meter.
Note: Pay attention to the physical limitations of data transmission on the M-Bus! For a larger number of meters, set the transmission speed on the meter to 9600 baud.
The baud rate, primary address, and parity should be configured using the hardware buttons. Refer to the Inepro PRO1-Mb manual for details.
– Scroll using the button to Program mode 3.
– Hold the button for 3 seconds to enter the menu.
– Enter the 4-digit password: scroll using the button to select each digit (0-9), then hold the button for 3 seconds to confirm each digit.
– Scroll to LCD page Baud rate (M bAud xxxx).
– Hold the button for 5 seconds to enter programming mode.
– The value starts blinking: select 9600 / 4800 / 2400 / 1200 / 600 / 300.
– Confirm the new setting by holding the button for 3 seconds.
– The LCD will show „OK“ when the setting is confirmed.
You can access the Perseus web interface in one of the following ways:
Use HWg-Config to find the IP address of the Perseus device on your local network.
Note: The computer and the Perseus device must be on the same network.
https://www.hw-group.com/software/hwg-config-udp-config
Open HWg-Config, find your Perseus device in the device list, and click its IP address.
If necessary, use the Filter option and click Find Devices.
The Perseus web interface will open in your web browser.
3b) Option B – Remote Config (SensDesk Technology portal)
If Remote Config is enabled, open the SensDesk technology portal.
Go to Devices, select the corresponding Perseus device, and click Remote Config.
The remote Perseus web interface will open.
In the Perseus web interface, go to System.
Click Check for update and, if available, click Download & Upgrade.
5) Adding the Inepro PRO1-Mb Meter to Perseus
Open the Perseus web interface (local access or Remote Config).
Go to Monitoring → Meters → M-Bus. Click Scan.
Set the Serial baudrate to 2400 (or the value you already configured).
Set the Serial parity to Even. Click M-Bus Scan.
Select the detected M-Bus meter by checking the checkbox and save it.
Then Click on the newly detected meter for further configuration.
– Name = set a meaningful name (recommended if multiple meters are used)
– Measure period = 300 (or adjust if needed)
Then click Scan variables to add measured values.
Note: If multiple meters are connected, it is recommended to load values one meter at a time and rename the variables for easier identification later. Variable names are also transferred to the portal.
Go to Monitoring → Meters → M-Bus → select M-Bus meter → click Scan variables
The Import variables table will be displayed.
Select the values you want to use by checking.
7) Adjust parameters for individual variables
In the Variables section, click the corresponding Variable (measured value) if adjustments are needed.
Edit the Name field and enter a custom name for easy identification.
If required, adjust the Decimal digits, Unit and Value Multiplier.
To display the value in the portal, enable Push enable in the Portal settings section.
Repeat these steps for all enabled variables from the meter.
In the portal, open Meters and click your Inepro PRO1-Mb meter.
Click Edit and set the device name in the Alias field.
9) Configure Sensors Values in the Portal
In the portal, open Devices and click your Perseus device.
Under your device or meter, you will see the individual sensors/values.
Click a value name to open the sensor/value detail view.
Alias – set a custom sensor/value name (the original name is shown in the Name field)
Assign a permission group to each sensor/value. If no permission group is assigned, the sensor/value will be visible to all users within the Team.
The Perseus device reads values from the electricity meter via M-Bus protocol based on the configured parameters. These values can then be reported to the SensDesk Technology portal.
scanned all available M-Bus variables from the Inepro electricity meter
selected which values should be used in Perseus
transferred the selected values to SensDesk via LAN or LTE
In the portal, you can display graphs, monitor consumption, and analyse energy usage.